Welcome to the Schneider Electric Digest! O ve r a t h o u sa n d p a g e s o f t e ch n i ca l p r o d u ct i n f o r m a t i o n t o h e l p yo u sp e c i f y a n d se l e ct S ch n e i d e r E l e ct r i c p r o d u ct s. A ke y e l e m e n t o f t h e D i g e st ca t a l o g i s i t s co l o r - co d e d T a b l e o f C o n t e n t s, s h o w n a t t h e r i g h t , a n d m a t ch i n g p r o d u ct se ct i o n t a b s t h r o u g h o u t t h e D i g e st . T h i s co l o r f u l a p p r o a ch a i d s n a vi g a t i o n a n d h e l p s yo u q u i ckl y f i n d t h e m a j o r p r o d u ct ca t e g o r i e s. A l so , e a ch p r o d u ct se ct i o n b e g i n s w i t h a d e t a i l e d T a b l e o f C o n t e n t s a n d t h e r e a r e t w o p r o d u ct l o ca t o r i n d e xe s i n t h e b a ck o f t h e b o o k: a n a l p h a b e t i ca l l i st i n g a n d a n a l p h a - n u m e r i c l i st i n g . T h e l a t e st p r i ci n g i n f o r m a t i o n i s a va i l a b l e o n l i n e a t se . co m / u s. F i n a l l y, t h e S u p p l e m e n t a l a n d O b so l e sce n ce D i g e st ( o n l i n e o n l y) co n t a i n s a d d i t i o n a l p r o d u ct i n f o r m a t i o n f o r so m e o f o u r i n t e r n a t i o n a l p r o d u ct o f f e r s , l e g a cy p r o d u ct s, a n d p r o d u ct s i n t h e o b so l e sce n ce p r o ce ss.

1 2 3 4 5 6 7 8 9

Load Centers

Metering Equipment

Safety Switches

Power Monitoring and Control

Protection, Control, and Energy Automation

DigestPLUS Online Catalog

Surge Protective Devices

V i si t DigestPLUS o n l i n e f o r e a sy a cce ss t o t h i s ca t a l o g ( co n t i n u o u sl y u p d a t e d ) a n d a va i l a b l e i n b o t h P D F a n d m o b i l e - f r i e n d l y H T M L 5 f o r m a t s. T h e D i g e st P L U S si t e a l so p r o vi d e s q u i c k a cce ss t o t h e S u p p l e m e n t a l a n d O b so l e sce n ce D i g e st , p r o d u ct se l e ct o r s, a n d o t h e r r e l a t e d d o cu m e n t s a n d t o o l s. s e . c o m / u s / d i g e s t p l u s

Miniature and Molded Case Circuit Breakers Operator Mechanisms and Disconnect Switches

Services Across the Entire Equipment Lifecycle

Panelboards

S ch n e i d e r E l e ct r i c S e r vi ce s h e l p s d e si g n , m o d e r n i ze , m a i n t a i n , a n d m o n i t o r y o u r e l e ct r i ca l a sse t s a n d syst e m s f o r sa f e , r e si l i e n t , a n d su st a i n a b l e o p e r a t i o n s 24 / 7 se . co m / u s/ se r vi ce s EcoConsult se r vi ce s h e l p yo u i d e n t i f y p o t e n t i a l s a f e t y, co m p l i a n ce , a n d p e r f o r m a n ce i ssu e s t o r e d u ce r i sk a n d i m p r o ve r e l i a b i l i t y. O u r so l u t i o n s i n cl u d e d i g i t a l t w i n , st u d i e s, a u d i t s, a n d d e si g n . EcoCare m e m b e r sh i p h e l p s yo u r e d u ce u n p l a n n e d d o w n t i m e a n d m a i n t e n a n ce a ct i vi t i e s a n d e xt e n d t h e l i f e t i m e o f yo u r e q u i p m e n t . A cce ss f a st p r i o r i t y su p p o r t , 24 / 7 m o n i t o r i n g , se r vi ce s d i sco u n t s, a n d m o r e . EcoFit ™ o u r u n i q u e a p p r o a ch t o m o d e r n i za t i o n a n d ci r cu l a r i t y se r vi ce s. O u t d a t e d e q u i p m e n t a n d i n st a l l a t i o n s w a st e e n e r g y, i n cr e a se o p e r a t i n g co st s a n d p u t yo u r b u si n e ss co n t i n u i t y a t r i sk e ve r y d a y.

10 11 12 13 14 15 16 17 18 19 20 22 21 23 24 25

Power Solutions: Integrated

Switchboards and Switchgear

Busway

Wire Management

Transformers

mySchneider

Motor Control Centers

Check order status, price, and availability

F o r t h e d i st r i b u t o r s a n d p a r t n e r s w h o o r d e r d i r e ct l y f r o m u s, m yS ch n e i d e r p o r t a l o f f e r s a cce ss t o : • R e a l - t i m e p r o d u ct p r i ce a n d a va i l a b i l i t y • S i m p l i f i e d q u o t e s i n t e r f a ce • O r d e r h i st o r y a n d sh i p p i n g d e t a i l s

NEMA Contactors and Starters

IEC Contactors and Starters

L o g i n o r R e g i st e r

se . co m / u s / e n / w o r k/ su p p o r t / m ysch

n e i d e r

AC Drives and Soft Starters

mySchneider app

Push Buttons and Operator Interface

D o w n l o a d t h e m yS ch n e i d e r a p p a n d l o g i n t o a cce 24 / 7 se l f - s e r vi ce , a n d q u i ck e xp e r t su p p o r t i n f o r m a t i o n .

ss t a i l o r e d se r vi ce s,

se . co m / u s/ e n / w o r k/ su p p o r t / m ysch

n e i d e r - a p p /

Relays and Timers

m yS ch n e i d e r a p p

Terminal Blocks

Self-Service and Support

Self-Service and Support Center

Machine Safeguarding Products

Q u i c k a c c e s s t o m a n y p o p u l a r s e l f - s e r v i c e t o o l s : C h a t w i t h a n E x p e r t • S e a r c h F A Q s • P r o d u c t S e l e c t o r s • C o m p e t i t i v e C r o s s R e f e r e n c e • P r o d u c t S u b s t i t u t i o n & R e p l a c e m e n t • D o w n l o a d C e n t e r • W h e r e t o B u y • P r o d u c t R e g i s t r a t i o n • L a y o u t F A S T • a n d m o r e !

Automation Products

Universal Enclosures

s e . c o m / u s / e n / w o r k / s u p p o r t /

S u p p o r t C e n t e r

A d d S ch n e i d e r E l e ct r i c p r o d u ct s t o yo u r b u i l d i n g a n d e l e ct r i ca l d e si g n s i n se co n d s, n o t m i n u t e s, w i t h t h e f r e e L a yo u t F A S T t o o l . L a yo u t F A S T i n t e g r a t e s w i t h A u t o d e sk R e vi t ® B I M so f t w a r e , so yo u ca n f i n d t h e r i g h t p r o d u ct a n d e a si l y a d d i t t o yo u r e xi st i n g R e vi t d e si g n . P r o d u ct S e l e ct o r s

EcoStruxure and Schneider Electric Services TM

LayoutFAST:

s e . c o m / u s / e n / p a r t n e r s / r e s o u r c e s / l a y o u t f a s t /

D o c u m e n t N u m b e r : 0 10 0 C T 24 0 1 © 20 24 S c h n e i d e r E l e c t r i c A l l R i g h t s R e s e r v e d

New Products Listing

Section 1 Load Centers Energy Center .......................................................... 1-41 Schneider Pulse CSED................................................ 1-41 Schneider Energy Monitor............................................. 1-48 Square D™ Control Relays ........................................... 1-48 Dimmers, Switches, and Outlets...................................... 1-49 Section 4 Power Monitoring and Control ION9000 Series Advanced Power Quality Meters ....................4-7 PowerLogic™ EM4900 Series Multi-Circuit Meters ................ 4-25 EcoStruxure™ Panel Server.......................................... 4-26 AccuSine PCSn Active Harmonic Filter (AHF) ...................... 4-43 PowerLogic™ AccuSine™ EVC+ .................................... 4-44 Schneider Inverter and Boost ........................................ 1-48

Section 18 AC Drives and Soft Starters Altivar™ Process 630/650............................................18-16

Section 19 Push Buttons and Operator Interface XB5R Plastic and XB4R Metal Wireless, Batteryless Push Buttons ............. ...... ...............................................19-41 XB5R and XB4R Accessories........................................19-42 ZBRN1 and ZBRN2 Access Points..................................19-42 XB7 Push Buttons.....................................................19-44 XB7 Illuminated Push Buttons with Projecting Push...............19-45 XB7 Pilot Lights........................................................19-45 XB7 Selector Switches and Key Switches..........................19-46 XB7 Mushroom Head Push Buttons.................................19-46

Section 5 Protection, Control, and Energy Automation

Section 20 Relays and Timers Harmony™ RXG Interface Relays.................................... 20-4 Harmony™ RUM Plug-In Relays ....................................20-11 Square D™ Universal Relays........................................20-23

The PowerLogic P5 Range..............................................5-3 Easergy™ T300 RTUs — Introduction............................... 5-36

Section 6 Surge Protective Devices (SPDs) and EasyUPS3S External Mount SPDs....................................................6-5 SDSA1175, SDSA Three-Phase, and SPDE Surge SPDs...............6-6 Section 11 Switchboards and Switchgear FlexSeT Switchboards (cULus Listed)............................... 11-2 SureSeT™ Medium Voltage Metalclad Switchgear (UL Listed) . 11-17 MotorSeT™ Medium Voltage Motor Controllers (UL Listed) ...... 11-44 Section 17 Contactors and Starters-IEC TeSys island Load Management System............................ 17-5 TeSys™ Deca Non-Reversing Contactors .........................17-10 TeSys™ Deca Overload Relays .....................................17-11 TeSys™ Deca Reversing Contactors ...............................17-12 TeSys™ Giga Non-Reversing Contactors ..........................17-13 TeSys™ Giga Overload Relays......................................17-14 TeSys™ Giga Reversing Contactors................................17-14 TeSys™ Power Motor Circuit Breakers .............................17-30

Section 23 Automation Products Modicon™ M262 Logic/Motion Controller ........................... 23-4 Harmony ST6 Basic HMI .............................................. 23-7 Harmony GTUX™ Universal Panels ................................23-11 Harmony P6 Modular Box PCs and Displays ......................23-13 Modicon™ TM3 Bus Coupler Modules..............................23-17 Lexium Cobot (Collaborative Robots)...............................23-20 M173 Logic Controllers ...............................................23-26

Section 24 Universal Enclosures

PanelSeT SFN Modular Steel Enclosures........................... 24-2

Not a comprehensive listing of new or recently enhanced products. Visit se.com/us for current information .

© 2024 Schneider Electric All Rights Reserved

Table of Contents Section1 Load Centers

EZ Selector - Selection Assistance

1-2

QO™ Miniature Circuit Breakers

1-3

QO™ Load Centers

1-8

1 LOAD CENTERS

QO™ Miniature Circuit Breakers

Homeline™ Miniature Circuit Breakers

1-19

Homeline™ Load Centers 1-23 QO/Homeline Load Center Value Packs and Accessories 1-28 QO/Homeline Load Center Dimensions 1-34 Combination Service Entrance Devices (CSEDs) 1-37 Solar Ready Plug-On Neutral (PoN) CSEDs 1-45 Circuit Breakers for CSEDs 1-46 Accessories and Hubs for CSEDs 1-47 Schneider Energy Monitor %RRVW ,QYHUWHU 1-48 :LULQJ 'HYLFHV 1-

QO™ Load Centers

Homeline™ Miniature Circuit Breakers

Enclosed Devices

1-50

Homeline™ Load Centers

CSEDs

(QHUJ\ 0RQLWRU

6FKQHLGHU %RRVW DQG ,QYHUWHU

:LULQJ 'HYLFHV

© 2024 Schneider Electric All Rights Reserved

1-1

EZ Selector - Selection Assistance

Load Center EZ Selector - Selection Assistance

www.se.com/us

1 LOAD CENTERS

Services

QO™ and Homeline™ Load Center EZ Selector - Selection Assistance

EZ Selector Steps to select a load center. 1. Select product type:

• Homeline™ 1 inch format (HOM) • QO™ 3/4 inch format with plug-on neutral (QO) (P) • QO™ 3/4 inch format (QO) 2. Select enclosure type: indoor or outdoor (RB = rainproof) 3. Select single phase (1) or three phase (3) 4. Select type of main: • Main circuit Breaker (M) • Main lugs (L) • Generator panel (GP) 5. Select main ampacity rating 6. Select pole spaces and max. number of 1-pole, single-phase circuits 7. Select cover style: • Surface (box mounted on surface) • Surface (box mounted on surface, hinged cover included) • Flush (box recessed, cover is flush to wall) 8. Value pack (VP) 9. Select ground bar option: • Ground bar factory installed (T) • Ground bar included, field installation (G) 10. Select special application: • Riser panel with gutter • Mfg housing, single phase 3-wire, convertible mains • Manufactured housing, single phase, 3-wire • Manufactured housing, single phase, 2-wire

QO Load Center

QO™ and Homeline™ Load Centers — Catalog Number Description

QO

18 16 M100P C

Type

Covers and Construction

QO HOM

= QO = Homeline

= Qwik-Grip = Combination cover included = No cover, order cover separately = Rainproof = Hub ready = Ground bar factory installed = Ground bar included, field installed = Flush cover with door included = Surface cover included = Flush cover included = Feed-thru lugs factory installed

Q C Blank

Phase (only applies to QO)

R B T G

Blank or 1 3

= Single-phase = Three phase

Spaces

DF DS F FT

Maximum number of full-size single-pole circuit breaker spaces.

Circuits 1

NM CU GP WG RBR

= Non-metallic = Copper bus = Generator panel = Wide gutter = Rainproof accepts B-hubs with generator receptacle = Service upgrade ready = Value Pack with standard circuit breakers included = (3) 15 A arc fault circuit breakers included = (1) 15 A arc fault circuit breaker included

Maximum number of single-pole circuits when using tandem circuit breakers. Note: Number of circuits minus number of spaces equals number of tandem circuit breakers accepted.

EP VP AF 1A

Mains Type

M L

= Main circuit breaker = Main lugs

MS MQ DM

= 300 A or 400 A main circuit breaker = Three-phase main circuit breaker = Dual mains

Ampacity Mains rating

Plug-on Neutral

P Blank

= Plug-on Neutral Ready = Does not accept Plug-On Neutral Circuit Breakers

Additional Information • See Circuits [1] . • Search our technical FAQs page: https://www.se.com/us/en/faqs/home/ • Refer to catalog 1100CT0501.

[1] QO Plug-on neutral load center catalog numbers indicate the number of spaces only. The tables in this document containing QO plug-on neutral load centers list the maximum number of single-pole circuits when using tandem breakers.

1-2

© 2024 Schneider Electric All Rights Reserved

QO Plug-On Circuit Breakers

QO™ Miniature Circuit Breakers

Class 730, 731, 733 / Refer to Catalog: 0730CT9801

www.se.com/us

QO Standard Plug-On Circuit Breakers Square D brand QO miniature circuit breakers are plug-on products for use in QO and QON load centers, NQ panelboards, NQ OEM interiors or Speed-D™ switchboard distribution panels. Bolt-on QOB circuit breakers are for use in NQOB and NQ panelboards or interiors. [1] The Square D exclusive Qwik-Open™ mechanism, with a trip reaction within 1/60th of a second, is standard on all 1P 15 and 20 A QO circuit breakers.

Table 1.1: Standard QO Plug-On Circuit Breakers Amperes Rating [2] 1P—120/240 Vac 2P—120/240 Vac Common Trip

1 LOAD CENTERS

2P—240Vac [3] Common Trip

3P—240Vac Common Trip

10kAIR

QO110

QO210

QO310

10A 15A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A

QO115 [4] [5] QO120 [4] [5] QO125 [4] QO130 [4] QO135 [4] QO140 [4] QO145 OBS QO150 [4] QO160 [4] QO170 [4]

QO215 [4] QO220 [4] QO225 [4] QO230 [4] QO235 [4] QO240 [4] QO245 [4] QO250 [4] QO260 [4] QO270 [4] QO280 [4] QO290 [4] QO2100 [4] QO2110 [4] QO2125 [4] QO215VH [8] QO220VH [8] QO225VH [8] QO230VH [8] QO240VH [8] QO250VH [8] QO260VH [8] QO270VH [8] QO280VH [8] QO290VH [8] —

QO315 [4] QO320 [4] QO325 [4] QO330 [4] QO335 [4] QO340 [4] QO345 [4] QO350 [4] QO360 [4] QO370 [4] QO380 [4] QO390 [4] QO3100 [4]

QO215H QO220H

QO225H OBS

QO230H

QO240H

QO250H OBS QO260H OBS QO270H OBS QO280H OBS QO290H OBS

QO1P 1Space Required

QO2P 2Spaces Required

QO3P 3Spaces Required

— — — — — — — —

QO2100H

100A 110A 125A 150A 175A 200A

— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — —

— — — — —

QO2150 [4] [6] [7] QO2175 [4] [6] [7] QO2200 [4] [6] [7]

QO200

QO300 OBS

Molded Case Switch 60 A max.–240 Vac

22kAIR [4]

QO115VH [5] QO120VH [5]

QO315VH [8] QO320VH [8] QO325VH [8] QO330VH [8] QO340VH [8] QO350VH [8] QO360VH [8] QO370VH [8] QO380VH [8] QO390VH [8] QO3100VH [8]

15A 20A 25A 30A 40A 50A 60A 70A 80A 90A

QO130VH QO140VH

QO2200 2P 200 A 4 Spaces Required

QO160VH

— — — — — — — — — — — — — — — — — — —

QO2100VH [8] [9] QO2110VH [8] [9] QO2125VH [8] [9] QO2150VH [6] [8] [7]

100A 110A 125A 150A 175A 200A

— — — — — — — — — — — — — — —

QO2175VH OBS

QO2200VH [6] [8] [7]

42kAIR [4]

QOH240 OBS QOH245 OBS QOH250 OBS QOH260 [10]

40A 45A 50A 60A 70A 80A 90A

QOH270 QOH280 QOH290 QOH2100

100A 110A 125A

QOH2110 [10]

QOH2125

65kAIR [4]

QH215 OBS

QH115 OBS QH120 [5] QH125 OBS QH130 OBS

QH315 OBS QH320 OBS QH325 [10] QH330 OBS

15A 20A 25A 30A

QH220

QH225 OBS

QH230

OBS This product is obsolete.

Refer to page 7-2 for Interrupting Ratings, Accessories, and Dimensions.

[1] See Digest Section 1 for load centers and Section 9 for panelboards and interiors. [2] 10–30 A circuit breakers are suitable for use with 60 o Cor 75 o C conductors. 35–125 A circuit breakers are suitable for use with 75 o C conductors. [3] UL Listed 5 k AIR on corner grounded Delta systems. [4] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers. [5] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads. [6] Requires four spaces (1 AWG–300 kcmil Al/Cu.) Suitable for switching 120 Vac fluorescent lighting loads. [7] Not suitable for use in 3Ø panels. Use only in 1Ø panel rated 150 A or greater. [8] UL Listed for use ahead of QO, QO-GFI, QO-EPD, QOT, QO-AFI, and QO-PL 10 k AIR circuit breakers to permit their application at 22 kA fault level. [9] 100 A maximum branch mounted opposite. [10] Order only. Contact your local Field Office.

1-3

© 2024 Schneider Electric All Rights Reserved

QO™ Miniature Circuit Breakers

QO Plug-On Circuit Breakers

Class 730, 731, 733 / Refer to Catalog: 0730CT9801

www.se.com/us

1 LOAD CENTERS

Table 1.2: QO/QOB 48 Vdc 5 kA Ampere Rating

Poles

Suffix 5272

10–60A

2

QO/QOB Ring Terminal Table 1.3: QO/QOB Ring Terminal—Factory-Installed Only Ampere Rating Poles

Suffix

1, 2, 3

10–30A 35–60A 35–50A 70–110A 60–100A

5237 5238

1,2

3 2

5273

3 Wire Sizes for QO/QOB Circuit Breakers Table 1.4: Wire Sizes for QO/QOB Circuit Breakers Circuit Breaker Type Ampere Rating [11]

WireSize (AWG/kcmil) 14–8Al/Cu (2) 14–10 Cu 8–2Al/Cu 14–8Al/Cu (2) 14–10 Cu 8–2Al/Cu 4–2/0 Al/Cu 4–300 Al/Cu 8–2Al/Cu 4–2/0 Al/Cu 4–300 Al/Cu

10–30A 10–30A 35–70A 10–30A 10–30A 35–70A 80–125A 150–200A 10–30A 35–70A 80–125A 110–150A 15–20A 15–30A 40, 50, 60A

QO 1P

QO 2P

14–8 Al/Cu, (2) 14-10 Cu

QO 3P

QOB-VH

QOT

12–8 Al 14–8 Cu 12–8 Al 14–8 Cu 12–4 Al 14–6 Cu 12–2 Al 14–2 Cu

QO-AFI, QO-GFI or QO-EPD

QO-PL

10–60A

QOT and QO Tandem Circuit Breakers

QOT tandem circuit breakers have a mounting cam as shown. Installation into a QO load center can only be made in those positions having a mounting pan rail slot. Meets Paragraph 408.54 of the NEC ® . UL Listed as Class CTL. Table 1.5: QOT Tandem Circuit Breakers (CTL)—Not Compatible with Plug-on Neutral Systems Ampere Rating [11] Cat.No. [12] 1P—120/240 Vac 15Aand15A QOT1515 15Aand20A QOT1520 20Aand20A QOT2020 2P—120/240 Vac Common Trip Order two QOT1515 or QOT2020 circuit breakers and handle tie QOTHT for common switching of center two poles. Table 1.6: QO Tandem Circuit Breakers (non-CTL)—Compatible with Plug-on Neutral Systems Ampere Rating [11] Cat.No. [12] 1P—120/240 Vac—1 Space Required 15Aand15A QO1515 15Aand20A QO1520 20Aand20A QO2020 20Aand30A QO2030 30Aand20A QO3020 Two 1P Individual Trip—120/240 Vac—2 Spaces Required 15Aand15A Order two QO1515 or QO2020 circuit breakers and handle tie QOTHT

QOT 1P Tandem 1 Space Required

Rail Bead Mounting Cam

Pan Rail Slot

15Aand20A 20Aand20A 20Aand30A 30Aand20A

QO20303020 [13]

— NOTE: The torque values for these products can be found at www.se.com

[11] 10–30 A circuit breakers are suitable for use with 60 o Cor 75 o C conductors. 35–125 A circuit breakers are suitable for use with 75 o C conductors. [12] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers. [13] Includes two circuit breakers (one QO2030 and one QO3020) and handle tie QOTHT.

1-4

© 2024 Schneider Electric All Rights Reserved

QO Plug-On Circuit Breakers

QO™ Miniature Circuit Breakers

Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801

www.se.com/us

QO Ground-Fault Circuit Breakers (GFI)

Qwik-Gard ™ circuit breakers provide overload and short circuit protection, combined with Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will trip when a fault current to ground is 6 mA or more, for people protection. Do not connect to more than 250 feet of load conductor for the total one-way run to prevent nuisance tripping. Table 1.7: QO-GFI Circuit Breakers

Qwik-Gard Circuit Breakers With Ground Fault Circuit Interrupter 1P120Vac 2P Common Trip 120/240 Vac 3PCommon Trip 208Y/120 Vac

1 LOAD CENTERS

Circuit Breaker Type

Ampere Rating [14]

10kAIR 1Space Required QO115GFI QO120GFI

10kAIR 3Spaces Required QO315GFI QO320GFI

1P QO-GFI

2P QO-GFI

22kAIR 1 Space Required

10kAIR 2 Spaces Required

QO115VHGFI QO120VHGFI

QO215GFI QO220GFI QO225GFI QO230GFI QO235GFI QO240GFI QO245GFI QO250GFI

15 20 25 30 35 40 45 50 60 15

— — — — — — — —

Ground-Fault Circuit Interrupter (Pigtail Neutral)

QO130GFI

QO330GFI

— — — — —

QO340GFI

QO350GFI

QO260GFI [15]

— —

Plug-On Neutral Ground-Fault Circuit Interrupter

QO115PGFI [16]

QO120PGFI [16]

20

QO Arc-Fault Circuit Breaker (QO-CAFI)

QO arc-fault circuit breakers provide protection for Series and Parallel Type Arcing as required by the NEC and local code adoption, and comply with UL1699. Table 1.8: QO-CAFI Circuit Breakers Circuit Breaker Type [17] Ampere Rating One–Pole 120 Vac Two–Pole 120/240 Vac 10kAIR 1 Space Required 22kAIR 1 Space Required 10kAIR 2 Space Required

Combination Arc fault Interrupter (Pigtail Neutral) Plug-On Neutral Combination Arc fault Interrupter

QO215CAFI [18] QO220CAFI [18]

QO115CAFI QO120CAFI QO115PAF QO120PAF

QO115VHCAFI QO120VHCAFI QO115VHPAF QO120VHPAF

15 20 15 20

1P QO-CAFI Pigtail

1P QO-CAFI Plug-On Neutral

QO Dual Function Circuit Breaker

QO Combination Arc Fault and Ground Fault Circuit Interrupters (Dual Function) provide overload and short circuit protection, plus arc fault and ground fault protection in accordance with the NEC, UL1699 and UL943. Table 1.9: QO-DF Circuit Breakers Circuit Breaker Type [17] Ampere Rating 1P120Vac 10kAIR 1 Space Required 1P120Vac 22kAIR 1 Space Required Combination Arc-fault and Ground Fault Circuit Interrupter (Pigtail Neutral) QO115DF QO120DF — QO120VHDF

15 20 15 20

Plug-On Neutral Combination Arc-fault and Ground Fault Circuit Interrupter

QO115PAFGF QO120PAFGF

QO115VHPAFGF QO120VHPAFGF

1PQO-DF Plug-on Neutral

1PQO-DF Pigtail

[14] 10–30 A circuit breakers are suitable for use with 60 o Cor 75 o C conductors. 35–125 A circuit breakers are suitable for use with 75 o C conductors. [15] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection. [16] New Plug-On Neutral [17] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers. [18] For 120/240 V only, not for 208Y/120 V.

1-5

© 2024 Schneider Electric All Rights Reserved

QO™ Miniature Circuit Breakers

QO Plug-On Circuit Breakers

Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801

www.se.com/us

1 LOAD CENTERS

QO-EPD/EPE Circuit Breakers

QO-EPD/EPE circuit breakers provide overload and short circuit protection combined with Class B ground fault protection. They are designed to provide ground fault protection of equipment at a 30 mA level (EPD) or 100 mA level (EPE). They are not designed to protect people from electrical shock. Table 1.10: QO-EPD Circuit Breakers Ampere Rating [19] 1P

2P Common Trip 120/240 Vac 10kAIR 2 Spaces Required

120Vac 10kAIR 1 Space Required

QO315EPE [20] QO320EPE [20] QO330EPE [20] QO340EPE [20] QO350EPE [20] —

QO115EPD QO120EPD

QO215EPD QO220EPD QO225EPD QO230EPD QO240EPD QO250EPD

15 20 25 30 40 50 60

QO125EPD OBS

QO130EPD

— — —

QO220EPD

QO260EPD [21]

OBS This product is obsolete.

QO Switch Neutral Common Trip Circuit Breakers (QO-SWN) Switch Neutral Common Trip 2008 NEC ® 514.11 Table 1.11: QO-SWN Circuit Breakers Ampere Rating [22] 2 Wire 120 Vac 10kAIR 2 Spaces Required 15 QO215SWN 20 QO220SWN QO High Intensity Discharge Circuit Breakers (QO-HID) HID circuit breakers are for use on circuits feeding fluorescent and high intensity discharge (HID) lighting systems such as mercury vapor, metal halide, or high pressure sodium. These circuit breakers are physically interchangeable with QO circuit breakers. Table 1.12: QO-HID Circuit Breakers Ampere Rating [22] 1P 120/240 Vac 10kAIR 2P Common Trip 120/240 Vac 10kAIR 3P Common Trip 240Vac 10kAIR QO High Magnetic Trip Circuit Breakers (QO-HM) High magnetic trip circuit breakers are recommended for applications where high initial inrush may occur and for individual dimmer applications. Table 1.13: QO-HM Circuit Breakers 120 Vac—10 k AIR Ampere Rating [22] 1P 15A QO115HM [23] [24] 20A QO120HM [23] [24] Non-Automatic (Standard) Miniature Switches Miniature non-automatic switches have the same physical packaging as miniature circuit breakers, but open only when the handle is switched to the OFF position. Non-automatic switches provide no overcurrent protection or short circuit protection. They must not be used on systems that have an available fault current greater than the values listed in the table. Non-automatic switches are UL Listed per UL 1087 and are CSA certified. Table 1.14: QO Non-Automatic Miniature Switches, 240 Vac 10 kA Ampere Rating 2P 3P 60 QO200 QO300 OBS OBS This product is obsolete. 20 — QO220HID QO320HID

QO320HID

[19] 10–30 A circuit breakers are suitable for use with 60ºC or 75ºC conductors. 35–125 A circuit breakers are suitable for use with 75ºC conductors. [20] See note in Instruction Bulletin when using in an enclosure with a QO403 or QON prefix. [21] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection. [22] 10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–60 A circuit breakers are suitable for use with 75oC conductors. [23] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers. [24] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.

1-6

© 2024 Schneider Electric All Rights Reserved

QO Accessories

QO™ Miniature Circuit Breakers

Class 1130 / Refer to Catalog 1100CT0501

www.se.com/us

Accessories for QO/QOB Circuit Breakers

Table 1.15: Accessories for use with QO and QOB Miniature Circuit Breakers Description

Cat.No.

Schedule

Handle Attachments HandleTie

QO1HT QOTHT QO3HT QO1LO HLO1 QOHPL QO1PA GFI2PA QO1HPL QO1PL QO2PAF

Converts any two adjacent 120/240 Vac 1P QO circuit breakers to independent trip 2P Converts any two adjacent 120/240 Vac1P side-by-side QOT circuit breakers to independent trip 2P Clamp for holding QO 1P handle in ON or OFF position Clamp for holding QO or Q1 either 1P, 2P or 3P circuit breaker handles in ON or OFF position

DE2E DE2E DE2E DE2E DE2E DE2E DE2E DE2A DE2E DE2E DE2E DE2E DE2E DE2A DE2A DE2A DE2A DE3 DE2E

Handle Clamp

For padlocking 1P QO circuit breaker in ON or OFF position Looseattachment Fixedattachment For padlocking 1P side-by-side QOT circuit breaker in ON or OFF position

1 LOAD CENTERS

Handle Padlock Attachment for Padlocking in ON or OFF position

QOTHPA OBS

For padlocking 2P QO-GFI circuit breakers in either ON or OFF position, fixed attachment. For 2P and 3P QO and Q1 standard circuit breakers which require padlocking in either ON or OFF position. Looseattachment Fixedattachment For padlocking 2P and 3P QO circuit breakers in OFF position only, fixed attachment. For padlocking 1P QO, QO-GFI, QO-CAFI, QO-DF and QO-EPD circuit breakers in OFF position only, fixed attachment. For padlocking 2P QO-GFI, QO-CAFI and QO-EPD circuit breakers in OFF position only, fixed attachment.

Handle Padlock Attachment for Padlocking in OFF position

QOADV1PAF QOGFI2PAF See Section 7 QO60SL OBS QO2125SL QO2225SL [25] QO3125SL

Ring Terminal

Ring terminals are available as a factory-installed option. 60 A 2P plug-on – 2 spaces required (6–2 Al/Cu) 125 A 2P plug-on – 2 spaces required (12–2/0 Al/Cu) 225 A 2P plug-on – 4 spaces required (4–300 Al/Cu) 125 A 3P plug-on – 3 spaces required (12–2/0 Al/Cu)

Sub-feed Lugs

For interlocking the handles of two 2P or one 2P and one 1P QO and Q1 circuit breakers mounted side-by-side so that only one circuit breaker can be ON at a time (Not QOU) QO2DTI mechanical interlock attachment with retaining kits for securing two adjacent back-fed circuit breakers in dual power supply applications. Can be used with (2) 2Ps or (1) 2P and (1) 1P QO circuit breakers in QO816L100 load centers.

Mechanical Interlock Attachment With Retaining Kit

QO2DTI

QO2DTIM

DE2E

OBS This product is obsolete.

QO1PA

QO1PL

QO1HT

HLO1

QO1PAF

QO2DTI

QO1HPL

QOTHPA

QOADV1PAF

QO1LO

QOHPL

QO2PAF

[25] Not suitable for use in 3Ø panels. Use only in 1Ø panel rated 150 A or greater.

1-7

© 2024 Schneider Electric All Rights Reserved

QO™ Load Centers

QO Indoor Load Centers, Single Phase Class 736, 1130 / Refer to Catalog 1100CT0501

www.se.com/us

1 LOAD CENTERS

Factory-Installed Accessories for QO and QOB Miniature Circuit Breakers Factory-installed electrical accessories take up an additional pole space on QO, QO GFI, QO-EPD, QO-SWN and QOU circuit breakers. All AC electrical accessories shown below are rated for 50/60 Hz. Accessories are not available for QOB-VH (2P 150 A and 3P 110–150 A) circuit breakers or QO, QOU molded case switches. QO circuit breakers will accept only one accessory per circuit breaker. Undervoltage trip is not available on miniature circuit breakers. Factory-installed accessories are not available for QO-AFI or QO-CAFI Arc Fault Circuit Breakers, QO-CAFI, QO-DF, or QO-PDF circuit breakers, or on QO2150, QO2175, or QO2200 circuit breakers.

Table 1.16: Factory-Installed Accessories for QO/QOB Circuit Breakers [26] Accessory Description Rated Voltage Coil Burden Cat. No. Suffix Accessory

Cat. No. Suffix

Max. Voltage Max.

Contact Comb.

Description

Trips the circuit breaker from a remote location by means of a trip coil energized from a separate circuit. A 120 Vac shunt trip will operate at 55% or more of rated voltage. All other shunt trips will operate at 75% or more of rated voltage. Application • For use with momentary or maintained push button. • Not available on QO-GFI, QO EPD. QO-AFI, QO-CAFI, QO DF, or QO-PDF. • Shunt trip terminals accept (2) 0.14– 0.12 AWG Cu.

Monitors circuit breaker contact status and provides a remote signal indicating the circuit breaker contacts are OPEN or CLOSED. Application • Auxiliary switch terminals accept (2) 14–12 AWG Cu leads. • Leads (EH): Yellow for “A’’, Blue for “B’’, Striped common 18 AWG Cu. Used with control circuits and is actuated only when the circuit breaker has tripped. Standard construction includes a normally-open contact. Application • Leads: Alarm switch terminals accept (2) 14–12 AWG Cu leads.

1A 1B

120Vac 120Vac

5A 5A

-1200 -1201

12Vac/Vdc 24Vac/Vdc

60VA 168 VA -1042

Auxiliary Switches

Shunt Trip

120Vac 208Vac 240Vax

72VA 228VA 288VA

Alarm Switches

-1021

1A 120 Vac 5 A -2100

Plug-on Neutral Load Center Main Lugs, Convertible Mains Single Phase 3W—120/240 Vac Indoor—UL Listed QO Plug-on Neutral Load Centers and CAFI Breakers are engineered for a quick Plug on Neutral connection on every unit. Table 1.17: Convertible Main Lugs Plug-on Neutral Load Center (Compatible with QO Plug-on Circuit Breaker and QO Plug-on Neutral Circuit Breakers)

Max. Single Pole Circuits [1]

Load Center Covers

Max. Tandem Circuit Break ers

Equipment Ground Bar Kit (Factory Included)

Mains Rating

Box No. [2]

Spac es

Load Center Box and Interior

Al

CU Bus Rating

Flush/Surface

Mono-Flat

Convertible Mains—Factory-installed Main Lugs — 65 kA Short Circuit Current Rating—Copper Bus QOM1 Main Frame Size—Convertible to Main Circuit Breaker

QO112L125PG QOC16UF [3] QOC16US QO116L125PG QOC24UF [3] QOC24US QO120L125PG QOC20U100F [3] QOC20U100S QO124L125PG QOC24UF [3] QOC24US QO130L125PG QOC30U125C QO132L125PG QOC32UF [3] QO124L200PG QOC30UF [3] QOC30US QO130L200PG QOC30UF [3] QOC30US QO140L200PG QOC40UF [3] QOC40US QO142L225PG QOC42UF [3] QOC42US QO154L225PG QOC54UF [3] QOC30UF [3] QOC30US

6–2/0

125

PKGTALP1

6

12

24

12

16

24

8

6–2/0

125

PKGTALP1

7

20

24

4

6–2/0

125

PKGTALP1

6

125A

24 30 32

34 34 38

10

— — —

6–2/0 6–2/0 6–2/0

125 125 125

PK15GTAL PK23GTAL PKGTALP1

7 9 8

4 6

I N D O O R

Convertible Mains— Factory-installed Main Lugs, 65 kA Short Circuit Current Rating—Copper Bus QOM2 Main Frame Size—Convertible to Main Circuit Breaker

QOCMF30UCW [3]

QO112L200PG OBS

12

24

12

4–300 4–250

225

PKGTALP1

9

QOCMF30UCW [3]

24

36

12

4–300 4–250

225

PKGTALP1

9

200A

QOCMF30UCW [3]

30

40

10

4–250

225

PK23GTAL

9

40

60

20

4–300 4–250

225

PKGTALP2

10

QOCMF42UCW [3] QOCMF54UCW [3]

4–300 4–300

225 225

PK23GTAL PK23GTAL

11 11

42 54

52 64

10 10

225A

Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2. OBS This product is obsolete.

[26] QOB circuit breakers with shunt trip, auxiliary switches, and/or alarm switches, which are no longer active commercial references, may be available Factory Assembled into NQ Panelboards. [1] Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers. [2] See page 1-34 [3] Available in gray and white. For white equivalencies, add the “W” suffix to the reference, or see page 1-29.

1-8

© 2024 Schneider Electric All Rights Reserved

QO Indoor Load Centers, Single Phase Class 736, 1130 / Refer to Catalog 1100CT0501

QO™ Load Centers

www.se.com/us

Field-Installed Main Circuit Breaker Kits, 1Ø

Table 1.18: QOM1 Frame Size—Use with Convertible Main Load Centers Only Main Circuit Breaker Rating [4] Convertible Load Center Mains Rating 22kAIR [5] Lug Wire Size [6] AWG/ kcmil Main Circuit Breaker 50A 100–125 QOM50VH

QOM60VH QOM70VH QOM80VH QOM90VH QOM100VH QOM110VH QOM125VH

60A 70A 80A 90A

100–125 100–125 100–125 100–125 100–125

12–2/0 Al or Cu

QOM1 Frame Size 50–125 Amperes

100A 110A 125A

125 125

1 LOAD CENTERS

Table 1.19: QOM2 Frame Size—Use with Convertible Main Load Centers Only Main Circuit Breaker Rating [4] Convertible Load Center Mains Rating 22kAIR [5] Lug Wire Size [6] AWG/kcmil Main Circuit Breaker [7] 100A 150–225 QOM2100VH

QOM2125VH QOM2150VH QOM2175VH QOM2200VH QOM2225VH

125A 150A 175A 200A 225A

150–225 150–225 200–225 200–225

4–300 Al or Cu

225

QOM2 Frame Size 100–225 Amperes

Do not exceed the load center mains rating.

[4]

[5] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current. [6] Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find out maximum wire size permitted in a particular load center per UL, see Main Wire Size in that load center table. [7] Add suffix 1021 for 120, 208 or 240 Vac shunt trip.

1-9

© 2024 Schneider Electric All Rights Reserved

QO™ Load Centers

QO Indoor Load Centers, Single Phase Class 736, 1130 / Refer to Catalog 1100CT0501

www.se.com/us

1 LOAD CENTERS

Plug-on Neutral Load Center Main Breaker, Convertible Mains 1Ø3W—120/240 Vac Indoor—UL Listed QO Plug-on Neutral Load Centers and CAFI Breakers are engineered for a quick Plug on Neutral connection on every unit. Table 1.20: Convertible Main Breaker Plug-on Neutral Load Centers (Compatible with QO Plug-on Circuit Breakers and QO Plug-on Neutral Circuit Breakers)

Equipment GroundBar Kit (Order Separately)

Load Center Covers

Max. 1P Circuits

Max. Tandem Breakers

Mains Rating

Bus Rating

Box No. [8]

Space s

Load Center Box and Interior

Al

Cu

Flush/Surface

Mono-Flat

Convertible Mains — Factory-Installed Main Circuit Breaker— 22 kA Short Circuit Current Rating Convertible to Main Lugs (see below) or Lower Amperage Main Circuit Breaker (see QO Standard Plug-On Circuit Breakers, page 1-3) [9] , QOM1 Main Circuit Breaker Frame Size—Copper Bus

QOC12UF QOC12US

QO112M100P

12

24

12

6-2/0 6–1

125

PK9GTA

5

QO116M100P QOC20U100F [10] QOC200U100S QO120M100P QOC20U100F [10] QOC200U100S QO124M100P QOC24UF [10] QOC24US QO132M100P QOC32UF [10] QO124M125P QOC24UF [10] QOC24US QO132M125P QOC32UF [10] QO124M150P QOC30UF [10] QOC30US QO130M150P QOC30UF [10] QOC30US QO132M150P QOC40UF [10] QOC40US QO124M200P QOC30UF [10] QOC30US QO130M200P QOC30UF [10] QOC30US QO140M200P QOC40UF [10] QOC40US QO142M200P QOC42UF [10] QOC42US QO154M200P QOC54UF [10] QOC30UF [10] QOC30US QOC30UF [10] QOC30US

16

24

8

6-2/0 6–1

125

PK9GTA

6

100A

20

24

4

6-2/0 6–1

125

PK9GTA

6

24 32 24 32

34 38 34 38

10

— — — —

6-2/0 6-2/0 6-2/0 6-2/0

125 125 125 125

PK15GTA 7 PK15GTA 8 PK15GTA 7 PK15GTA 8

6

10

125A

6

Convertible Mains — Factory-Installed Main Circuit Breaker— 22 kA Short Circuit Current Rating Convertible to Main Lugs (see below) or Lower Amperage Main Circuit Breaker (see QO Standard Plug-On Circuit Breakers, page 1-3) [9] , QOM2 Main Circuit Breaker Frame Size—Copper Bus

QOCMF30UCW [10]

20

30

10 QO120M150P OBS

4-250

225

PK15GTA 9

I N D O O R

QOCMF30UCW [10]

24

36

12

4-250

225

PK15GTA 9

150A

QOCMF30UCW [10]

4-250

225

PK15GTA 9

30

40

10

32

40

10

4-300

4-250 225

PK15GTA 10

QOCMF30UCW [10]

20

30

10 QO120M200P OBS

4-300

4-250 225

PK15GTA 9

QOCMF30UCW [10]

4-300

4-250 225

PK15GTA 9

24

36

12

QO154M200P

QOCMF30UCW [10]

30

40

10

4-250

225

PK15GTA 9

200A

40

60

20

4-300

4-250 225

PK23GTA 10

QOCMF42UCW [10] QOCMF54UCW [10]

4-300 4-300 4-300

225 225 225

PK18GTA 11 PK23GTA 12 PK27GTA 24

42 54 60

52 72 72

10 18 12

QO160M200PC [11]

QOC42UF [10] QOC42US

QOCMF42UCW [10]

40

60

20 QO140M225P OBS

4-300

225

PK23GTA 11

225A

QO142M225P QOC42UF [10] QOC42US

QOCMF42UCW [10]

4-300

225

PK18GTA 11

42

52

10

Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2. OBS This product is obsolete.

Field-Installed Main Lugs Kits, 1Ø

Table 1.21: 1Ø Field-Installed Main Lug Kits—Use with Convertible Main Load Centers Only

Useon Convertible Load Center with Mains Rating

Lug Wire Size [13] AWG/kcmil Al orCu

MainLugs Rating [12]

Cat. No.

QOL125 [14]

125A 125A 225A

100–125A 100–125A 150–225A

6–2/0 6–4/0 6–300

QOL125VD [14]

QOL225 [14]

QOL125

QOL225

[8] See Indoor Knockout Information and Enclosure Dimensions, page 1-34. [9] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current. [10] Available in gray and white. For white equivalencies, add the “W” suffix to the reference, or see page 1-29. [11] For Certification to IEC 60439-1 contact the local Square D sales office; otherwise panels are NOT CE marked. (For use on 415Y/240 Vac 3-phase 4-wire, 3,000 Short Circuit Current Rating when QOXD...branch circuit breakers are used and 10,000 Short Circuit Current Rating when QO...VS branch circuit breakers are used). [12] Do not exceed the load center mains rating. [13] Wire range listed for QOL lug kits is the wire range of that lug. To find out maximum wire size permitted in a particular load center per UL, see Main Wire Size in that load center table. [14] If main circuit breaker knockout has been removed from the load center’s trim, order appropriate filler plate from Table 1.51, page 1-25

1-10

© 2024 Schneider Electric All Rights Reserved

QO Indoor Load Centers, Single Phase Class 736, 1130 / Refer to Catalog 1100CT0501

QO™ Load Centers

www.se.com/us

QO™ Plug-On Neutral Load Centers with Qwik-Grip™ 1Ø3W—120/240 Vac Indoor—UL Listed The Square D QO plug-on neutral load centers with Qwik-Grip simplify rough-in by eliminating the need to remove knockouts, install wire connectors, and blindly pull wire into the load center. A quick bend of the wire using the wire bend guide on the Qwik-Grip insert and the wire slides into the slot. Once inserted, the Qwik-Grip shield snaps on to keep the wire behind the router for a secure, code-compliant installation.

1 LOAD CENTERS

QO Plug-on Neutral Load Center with Qwik-Grip™

Table 1.22: Plug-on Neutral Load Centers with Qwik-Grip (Compatible with QO Plug-on Circuit Breakers and QO Plug-on Neutral Circuit Breakers) Mains Rating Space s Max. Single Pole Circuits Max. Tandem Circuit Breakers Load Center Box and Interior Indoor Cover with Door (Order Separately) Main Wire Size AWG/kcmil Bus Rating Equipment Gound Bar Kit Box No. Flush/Surface Mono-Flat Al Cu Convertible Mains—Factory-Installed Main Lugs, 65 kA Short Circuit Current Rating—Copper Bus, QOM1 Main Frame Size, Convertible to Main Circuit Breaker

PK15GTAL Included PK23GTAL Included PK23GTAL Included PK23GTAL PK23GTAL Included PK23GTA (Order separately) PK23GTA (Order separately) PK23GTA (Order separately)

QO124L125PQG QOC24UF [15] QOC24US

7Q

125

24

34

10

125A

6–2/0

9Q

QO130L125PQG OBS

QOC30U125C

30

34

4

125

Convertible Mains-Factory—Installed Main Lugs, 65 kA Short Circuit Current Rating—Copper Bus, QOM2 Main Frame Size, Convertible to Main Circuit Breaker 200A 30 40 10 QO130L200PQG QOC30UF [15] QOC30US — 6–300 225

9Q

QO142L225PQG QOC42UF [15] QOC42US

I N D O O R

9Q

42

52

10

225

225A

54 12Q Convertible Mains—Factory-Installed Main Circuit Breaker, 22 kA Short Circuit Current Rating—Copper Bus, QOM2 Main Frame Size, Convertible to Main Lugs or Main Circuit Breaker 72 18 QO154L225PQG OBS QOC54UF [15] — 6–300 225

QOC30UF [15] QOC30US QOC42UF [15] QOC42US

QO130M200PQ

11Q

30

40

10

225

4–250

QO142M200PQ

11Q

200A

42

52

10

225

QOC54UF [15]

QO154M200PQ OBS

12Q

54

72

18

4–250

225

OBS This product is obsolete.

[15] Available in gray and white. For white equivalencies, add the “W” suffix to the reference, or see page 1-29.

1-11

© 2024 Schneider Electric All Rights Reserved

QO™ Load Centers

QO Load Centers, Rainproof, Single Phase

Class 1130 / Refer to Catalog 1100CT0501

www.se.com/us

1 LOAD CENTERS

QO Load Centers with Included Cover 1Ø3W—120/240 Vac Indoor—UL Listed Table 1.23: Load Centers with Included Cover (Compatible with QO Plug-on Circuit Breakers and QO Plug-on Neutral Circuit Breakers) Mains Rating Short Circuit Current Rating Spaces Max. 1P Circuits [16] Max. Tandem Circuit Breakers Load Center [17] Box, Interior, and Cover Al Cu Bus Rating Equipment Ground Bar Kit BoxNo. [18]

PKGTALP1 Included PKGTALP1 Included PK15GTA, LK100AN Included PK23GTA, LK100AN Included PK23GTA, LK100AN Included PK23GTA, LK100AN Included PK9GTA PK9GTA PK9GTA PK15GTA PK15GTA PK18GTA PK15GTA PK23GTA PK18GTA PK23GTA

QO112L125PGC

5

65kA

12

24

12

6-2/0

125

QO120L125PGC OBS

65kA

20

24

4

6-2/0

125

6

125A

QO124L125PGC

65kA

24

34

10

6-2/0

125

7

Convertible Mains—Factory-Installed Main Lugs [19] —QOM2 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-3)—Copper Bus 200A 65kA 30 40 10 QO130L200PGC 4-250 225

9

QO142L225PGC

65kA

42

52

10

4-300

225

11

225A

QO154L225PGC OBS

65kA

54

72

18

4-300

225

12

Convertible Mains—Factory-Installed Main Circuit Breaker— QOM1 Main Frame Size—Convertible to Main Lugs (See page 1-25 or Lower Amperage Main Circuit Breaker (See page 1-3)—Copper Bus [8][20]

QO112M100PC QO116M100PC OBS QO120M100PC QO124M100PC

22kA 22kA 22kA 22kA

12 16 20 24

24 24 24 34

12

6–2/0 6–2/0 6–2/0

6–1 6–1 6–1

125 125 125 125

5 6 6 7

8 4

100A

10

4-300

Convertible Mains—Factory-Installed Main Circuit Breaker— QOM2 Main Frame Size—Convertible to Main Lugs (See page 1-25 or Lower Amperage Main Circuit Breaker (See page 1-3)—Copper Bus [8][20] 150A 22kA 30 40 10 QO130M150PC 4-250 225

9

QO142M150PC QO130M200PC QO140M200PC QO142M200PC QO154M200PC

22kA 22kA 22kA 22kA 22kA

42 30 40 42 54

52 40 60 52 72

10 10 20 10 18

4-300 4-250 4-300 4-300

225 225 225 225 225

11

9

4-300

4-250

10 11 12

200A

OBS This product is obsolete.

Plug–on Neutral Load Center Main Lugs, Convertible Mains 1Ø3W—120/240 Vac Rainproof—UL Listed QO Plug-on Neutral Load Centers and CAFI Breakers are engineered for a quick Plug on Neutral connection on every unit. Table 1.24: Convertible Main Lugs Plug-on Neutral Load Center (Compatible with QO Plug-on Circuit Breakers and QO Plug-on Neutral Circuit Breakers) Mains Rating Spaces Max. Load Center Box and Interior Al Cu Bus Rating Equipment Ground Bar Kit (Factory Included) BoxNo. [21] Single Pole Circuits [16]

Max. Tandem Circuit Breakers

Convertible Mains — Factory-Installed Main Lugs — 65 kA Short Circuit Current Rating [22][19][23] QOM1 Main Circuit Breaker Frame Size, Convertible to Main Circuit Breaker — Equipment Ground Bar Included

R A I N P R O O F

QO112L125PGRB QO116L125PGRB QO124L125PGRB

12 16 24

24 24 34

12

6–2/0 6–2/0 6–2/0

125 125 125

PKGTALP1 PKGTALP1 PK15GTA

3R 4R 4R

125A

8

10

Convertible Mains — Factory-Installed Main Lugs — 65 kA Short Circuit Current Rating [22][19][23] QOM2 Main Circuit Breaker Frame Size, Convertible to Main Circuit Breaker — Equipment Ground Bar Included

QO112L200PGRB QO130L200PGRB QO140L200PGRB QO142L225PGRB

4–300

4–250

225 225 225 225

PKGTALP1 PK23GTAL PKGTALP2

5R 6R 7R 8R

12 30 40 42

24 40 60 52

12 10 20 10

200A

4–250

4–300

4–250

PK23GTA, LK100AN

225A

4–300

Above listings through 200 A mains rating meet Federal Specification W-P-115C as Type 1, Class 2.

[16] Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers. [17] Order F for flush device or S for surface device. [18] See page 1-34 [19] UL Listed 5000 A short circuit current rating for corner grounded Delta systems. Use QO-H circuit breakers only. [20] [9] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current. [21] See Enclosure Dimensions, page 1-36 or Indoor Enclosure Dimensions and Knockout Information, page 1-34 [22] UL short circuit current rating depends on lowest interrupting rating of circuit breaker installed. [23] Side hinge door device; allow 1-1/4 in. on left side for door to open.

1-12

© 2024 Schneider Electric All Rights Reserved