SE Modicon M580 Brochure
Modicon M580 automation platform Safety Modicon M580 Safety redundant processors (HSBY)
Presentation
Presentation Overview
1
The Modicon M580 Safety is a Modicon M580 programmable automation controller (PAC) with embedded safety modules and functions; it is available as a standalone PAC or a redundant PAC (HSBY) . A redundant PAC (HSBY) is based on two identically configured CPUs linked to each other and to the same remote I/O network. A safety coprocessor is mandatory for dual execution; if one CPU stops communications, the other assumes control of the I/O system. It is based on Modicon X80 modules and the EcoStruxure Control Expert (1) environment: b Modicon M580 Safety CPU and coprocessor b Redundant safety power supplies b Safety local and remote I/O b Safety communications b Software libraries for process and machine safety Modicon X80 Safety modules are only compatible with the Modicon M580 Safety processor. In a high availability architecture (HSBY), it is not possible to place I/O and Expert modules in the local rack (together with a CPU). Architecture The Modicon M580 Safety PAC is a safety-related system certified by TÜV Rheinland. It ensures safe operation while optimizing costs. The Modicon M580 Safety processor allows a mix of architectures:
Modicon M580 Safety configuration with the full safety rack
2
3
4
b It manages both Safety and non-Safety applications. b Safety and Process control functions are separate. b It integrates Process and Machine safety functions.
SCADA
5
CPS 4002S
CPS 4002S
P58 4040S
P58 CPROS3
NOC 0321
CPS 4002S
CPS 4002S
P58 4040S
P58 CPROS3
NOC 0321
HMI
Modicon X80 drop
6
SDO 0802
CPS 4002S
CPS 4002S
CRA 31210
SDI 1602
SAI 0410
SRA 0405
DOM 3202
CPS 4022
CPS 4022
CRA 31210
NOS 0300
AHI 0812
DDI 3202
AMI 0810
DOM 3202
Protection relay
SDO 0802
CPS 4002S
CPS 4002S
CRA 31210
SDI 1602
SAI 0410
SRA 0405
DOM 3202
EtherNet IP
I/O Module
Modbus
Motor pro tection
7
Variable speed drive
Power meter
Distributed devices
Modicon M580 Safety redundant topology
Safety level Modicon M580 Safety improves system reliability thanks to a unique combination of built-in cybersecurity and safety features:
8
b Isolated safety memory cells b Online error code correction
b Security watchdog b Clock monitoring b Safety application executed in a dedicated core b Memory isolation helping to secure access to safety and non-safety memory b Safety memory different from the standard CPU Any failure in the standard application does not impact the safety application. Safety applications using the M580 Safety PAC comply with: b up to Safety Integrity Level 3 (SIL3) for Industrial Process Safety regarding IEC61508/IEC61511 b up to Category 4, Performance Level «e» (Cat.4/PLe) for Machine Safety regarding ISO13849 b up to SILCL3 for Machine Safety regarding IEC62061 b up to SIL4 for Railway Safety regarding EN50126/EN50128/EN50129. The Safety level is achieved by dual execution of the safety application, using both the BMEH58 p 040S processor and the BMEP58CPROS3 coprocessor. (1) Unity Pro software in earlier versions.
9
10
3/12