SE Modicon M580 Brochure
Modicon M580 automation platform Modicon M580 standalone processors
Selection guide
Modicon M580 automation platform
BMEP5810 model
BMEP5820 models
BMEP5830 models
BMEP5840 models
BMEP5850 model
BMEP5860 model
1
1
2
2
Racks
8
Local racks (main + extension)
4
8
Not supported
16
Not supported
16
31
Remote I/O drops (1) Discrete I/O channels
Not supported
Local X80 I/O (2) (3)
1024
2048
3072
4096
5120
6144
Not supported
Safe discrete I/O channels
3
3
256
512
768
768
1024
1024
1280
1536
Analog I/O channels
Not supported
Safe analog I/O channels
108
108
144
144
180
216
Application-specific channels (4)
36
72
Combined Local and Remote X80 I/O (3)
10240
3072
19456
4096
20480
36864
37888
Discrete I/O channels
1024
2048
Safe discrete I/O channels
Not supported
2560
768
4864
1024
5120
9216
9472
Analog I/O channels
256
512
Safe analog I/O channels
Not supported
4
4
360
108 125 509
684
144 125 637
720
1296
1332
Application-specific channels (4)
36 61
72
Distributed equipment (DIO, CSIO)
61
61
61
EtherNet/IP or Modbus TCP devices (scanned by CPU)
125 381
317
445
573
EtherNet/IP or Modbus TCP devices (scanned by CPU and Ethernet modules)
BMENOC301/ BMENOC311
317
CIP safety devices (scanned by CPU)
Not supported
Integrated communication ports
Ethernet service port (RJ45)
Engineering and Maintenance console (EcoStruxure Control Expert, Web browser, external tools), HMI, SCADA, Distributed equipment (DIO)
5
5
Ethernet device network dual ports (RJ45) - RSTP
DIO network (DIO scanner)
RIO network (RIO/DIO scanner)
DIO network (DIO scanner)
RIO network (RIO/DIO scanner)
DIO network (DIO scanner)
RIO network (RIO/DIO scanner)
USB type mini B port
Programming port for Engineering Console (EcoStruxure Control Expert)
Communication
Cumulative max number of : Ethernet networks modules
BMENOC/BMENOP/ BMENOR
2
3
4
Ethernet networks
EtherNet/IP and Modbus TCP
EtherNet/IP and Modbus TCP module BMENOC0301
2 2 2 2 2 2 2 2 2
3 3
4 4
FactoryCast IP Forwarding
FactoryCast module Ethernet control router
BMENOC0311 BMENOC0321 BMENOP0300 BMENUA0100 BMENOR2200H BMXNOR0200H (5)
6
6
IEC 61850
IEC 61850 module OPC UA module
3
4
OPC UA
DNP3 Serial/NET, IEC60870-5-101/104 Advanced RTU module
3 3 3 6
4 4 4 8
DNP3 Serial / IEC 60870-5-101
RTU module
8
Global Data AS-Interface
Global Data module AS-Interface module Serial link module CANopen module PROFIBUS DP module Program process (MB)
BMXNGD0100 BMXEIA0100 BMXNOM0200 BMECXM0100 PMEPXM0100
7
7
4
4 (6)
6 (6)
8 (6)
Serial Link (Modbus and Character)
Each BMXNOM0200 channel counts as an application-specific channel Each BMECXM0100 counts as a Distributed equipment (DIO)
CANopen
PROFIBUS DP
2 4
4
6
10 64
Internal memory capacity
8
12
16
24
Data process (KB) Data storage (GB)
384
768
1024
2048
4096
Up to 64MB
4
8
8
No. of K instructions executed per ms
100% Boolean (Kinstr/ms)
10
20 15
40 30
50 40
65% Boolean + 35% fixed arithmetic (Kinstr/ms)
7.5 No
Product compatibility with Quantum
Support of Quantum Ethernet I/O (QEIO) and LL984 Editor
Yes
References
BMEP581020
BMEP582020
BMEP582040
BMEP583020
BMEP583040
BMEP584020
BMEP584040
BMEP585040
BMEP586040
Pages 2/7 (1) A Remote I/O drop can be either a X80 RIO Drop (RIO) or a Quantum Ethernet I/O drop (QEIO). One X80 RIO drop can support up to 2 racks (via X-bus extension). (2) Local X80 I/O are localized in local racks (main or extension). Redundant controllers do not not support Local X80 IO. (3) Maximum number of I/O channels (Discrete, Safe Discrete, Analog and Safe Analog) as well as application-specific channels is not cumulative. (4) Application-specific channels include counters, time-stamping, SSI encoder, Motion control, Serial and Frequency input modules. (5) Maximum number of BMXNOR modules is not cumulative with other Ethernet network modules. (6) With BMEP58 p 040 CPUs, additional BMXEIA0100 modules can be installed in remote drops : 2 per drop and with a maximum of 16 BMXEIA0100 modules.
9
9
10
10
More technical Information on www.se.com
More technical Information on www.se.com
2/2