Modicon M580 automation platform Standards, certifications, and environment conditions

Environment tests (continued)

Environment tests (continued) Name of test Electromagnetic emissions ( e ) (1) Conducted emissions

Standards

Levels

1

I EC/EN 61131-2; IEC/EN 61000-6-4; CISPR 11 & 22, Class A, Group 1 IEC/EN 61131-2; IEC/EN 61000-6-4; CISPR 11 & 22, Class A, Group 1

150 kHz … 500 kHz: quasi-peak 79 dB (µV/m); average 66 dB (µV/m) 500 kHz … 30 MHz: quasi-peak 73 dB (µV/m); average 60 dB (µV/m) 30 MHz ... 230 MHz: quasi-peak 40 dB (µV/m) (at 10 m/ 33 ft ) 230 MHz ... 1 GHz: quasi-peak 47 dB (µV/m) (at 10 m/ 33 ft ) 1 GHz ... 3 GHz: quasi-peak 76 dB (µV/m) (at 3 m/ 9.84 ft ) 3 GHz ... 6 GHz: quasi-peak 80 dB (µV/m) (at 3 m/ 9.84 ft )

Radiated emissions

2

Name of test

Standards

Levels

Immunity to climatic variations (1) (power on) Dry heat

IEC 60068-2-2 (Bb & Bd)

60 °C/ 140 °F , t = 16 hrs [for ruggedized range: 70 °C/ 158 °F , t = 16 hrs] (2) 0 °C…- 25 °C/ 32 °F...-13 °F , t = 16 hrs + power on at 0 °C/ 32 °F [for ruggedized range: power on at -25 °C/ -13 °F ] (2)

Cold

IEC 60068-2-1 (Ab & Ad)

3

Damp heat, steady state (continuous humidity)

IEC 60068-2-78 (Cab)

55 °C/ 131 °F , 93% relative humidity, t = 96 hrs [for ruggedized range: 60 °C/ 140 °F ] (2)

Damp heat, cyclic (cyclical humidity)

IEC 60068-2-30 (Db)

55 °C…25 °C/ 131 °F...77 °F , 93…95% relative humidity, 2 cycles t = 12 hrs +12 hrs 0 °C … 60 °C/ 32 °F...140 °F , 5 cycles t = 6 hrs + 6 hrs [for ruggedized range: - 25 °C…70 °C/ -13 °F...158 °F ] (2)

Change of temperature

IEC 60068-2-14 (Nb)

4

Name of test

Standards

Levels

Withstand to climatic variations (1) (power off) Dry heat

IEC/EN 61131-2; IEC 60068-2-2 (Bb & Bd) IEC/EN 61131-2; IEC 60068-2-1 (Ab & Ad) IEC/EN 61131-2; IEC 60068-2-30 (Db)

85 °C/ 185 °F , t = 96 hrs -40 °C/ -40 °F , t = 96 hrs

Cold

Damp heat, cyclic (cyclical humidity)

55 °C…25 °C/ 77 °F...131 °F , 93…95% relative humidity, 2 cycles t = 12 hrs + 12 hrs -40 °C...85 °C/ -40 °F...185 °F , 5 cycles t = 3 hrs + 3 hrs

5

Change of temperature (thermal shocks)

IEC/EN 61131-2; IEC 60068-2-14 (Na)

(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of PLC Systems” (see page 7/4). (2) Refer also to the section “Treatment for severe environments”. ( e ) : Tests required by European e directives and based on IEC/EN 61131-2 standards.