CHANNEL
PS 200 – 1 5 ⁄ 8 " x 1 5 ⁄ 8 " x 12 ga. See Pages 26-29
PS 100 – 1 5 ⁄ 8 " x 3 1 ⁄ 4 " x 12 ga. See Pages 22-23
PS 150 – 1 5 ⁄ 8 " x 2 7 ⁄ 16 " x 12 ga. See Pages 24-25
PS 210 – 1 5 ⁄ 8 " x 1 5 ⁄ 8 " x 14 ga. See Pages 30-31
PS 300 – 1 5 ⁄ 8 " x 1 3 ⁄ 8 " x 12 ga. See Pages 32 -33
PS 400 – 1 5 ⁄ 8 " x 1" x 12 ga. See Pages 34-35
PS 500 – 1 5 ⁄ 8 " x 13 ⁄ 16 " x 14 ga. See Pages 36-37
PS 520 – 1 5 ⁄ 8 " x 13 ⁄ 16 " x 12 ga. See Pages 38-39
PS 560 – 1 5 ⁄ 8 " x 13 ⁄ 16 " x 16 ga. See Pages 40-41
Maximum Allowable Pull-Out and Slip Loads
PS 600J – 13 ⁄ 16 " x 13 ⁄ 16 " x 19 ga. See Junior Channel Page 124
Channel Nut Size-Thread
Pull-Out Strength (Lbs.)
Resistance to Slip (Lbs.)
Torque Ft.-Lbs.
Allowable Gauge Channel
3 ⁄ 4 "-10 5 ⁄ 8 "-11 1 ⁄ 2 "-13 7 ⁄ 16 "-14 3 ⁄ 8 "-16 5 ⁄ 16 "-18 1 ⁄ 4 "-20 1 ⁄ 2 "-13 3 ⁄ 8 "-16 5 ⁄ 16 "-18 1 ⁄ 4 "-20 1 ⁄ 2 "-13 3 ⁄ 8 "-16 5 ⁄ 16 "-18 1 ⁄ 4 "-20 1 ⁄ 2 "-13 3 ⁄ 8 "-16 5 ⁄ 16 "-18 1 ⁄ 4 "-20
2,500 2,500 2,000 1,400 1,000
1,700 1,500 1,500 1,000
*125 *100
12 Gauge PS 100 PS 150 PS 200 PS 300 12 Gauge PS 400 PS 520 14 Gauge PS 210 PS 500
50 35 19 11 50 19 11 50 19 11 50 19 11 6 6 6
800 500 300 800 500 300 750 400 300 750 400 300
800 600
1,500 1,000
1,500
800 600
PS 700J – 13 ⁄ 16 " x 13 ⁄ 32 " x 19 ga. See Junior Channel Page 125
1,400 1,000
1,000
800 600
1,000 1,000
1,000
16 Gauge PS 560
800 600
6
* May require 3 ⁄ 8 " or 1 ⁄ 2 thick fitting. Nut design loads include a minimum safety factor of 3. Note: Refer to the Channel Nut Selection Chart on page 44 for the part number