PowerStrut Catalog

1 5 ⁄

8 "

Technical Data

7 ⁄

8 "

Design Load Data For Power-Strut Channel Connections

1 ⁄

2 "

1 ⁄

2 "

PS 603 – PS-200 1500#, PS-210 1000#

PS 605 – PS-200 1500#, PS-210 1000#

Load (lbs) 1,500

Channel

LOAD

Load (lbs) 1,500 1,000

Channel

PS 200

PS 200 PS 210

PS 210

1,000

Both Ends Supported

Both Ends Supported

PS 603 – PS-200 1000#, PS-210 650#

PS 3373 – PS-200 3000#, PS-210 2000#

LOAD

Load (lbs) 1,000

Load (lbs) 3,000

Channel

Channel

PS 200

PS 200

PS 210

650

PS 210

2,000

Both Ends Supported

Both Ends Supported

PS 745 – PS-200 2000#, PS-210 1500#

PS 607 – PS-200 2000#, PS-210 2000#

LOAD

LOAD

Load (lbs) 2,000

Load (lbs)

Channel

Channel

Tech. Data Fiberglass Power-Angle Jr. Channel Unipier ® Solar Components Concrete Inserts Electrical Pipe & Conduit Clamps Fittings Fasteners Metal Channel

PS 200

PS 200

2,000

PS 210

1,500

PS 210

Both Ends Supported

Both Ends Supported

PS 604 – 500#

PS 606 – 500#

PS-601 – PS-210 1000#, PS-210 800#

LOAD

Load (lbs) 1,000

LOAD

Channel

PS 200

PS 210

800

Both Ends Supported

1.) Safety Factor = 2 1 ⁄ 2 based on ultimate strength of connection. 2.) Load Diagrams indicate design loads for 12 ga. (listed as PS-200) and for 14 ga. (listed as PS-210) channels.