PowerLogic Catalog 2021
BASIC ENERGY METERING
DIMENSIONS AND CONNECTION
PowerLogic ™ PowerTag Energy 63 A
Technical specifications Main characteristics Rated voltage
1P+N / 1P+W Un
Phase-to-neutral Phase-to-phase Phase-to-neutral Phase-to-phase Phase-to-phase Phase-to-neutral Phase-to-neutral Phase-to-phase
200… 240 V AC ± 20 % 380… 415 V AC ± 20 % 220… 240 V AC ± 20 % 380… 415 V AC ± 20 % 200… 240 V AC ± 20 % 100… 127 V AC ± 20 % 120… 137 V AC ± 20 % 208… 240 V AC ± 20 %
3P
Un Un
3P+N
A9MEM1543 Un A9MEM1564 Un A9MEM1574 Un
Frequency
50/60 Hz
Maximum current
Imax
63 A 10 A
Basic current
Ib
Saturation current
130 A y 1 VA y 2 VA 40 mA
Maximum consumption
1P+N
3P/3P+N
Starting current
Ist
Additional characteristics Operating temperature
-25°C to +60°C -40°C to +85°C
Storage temperature Overvoltage category Measuring category
As per IEC 61010-1
Cat. III Cat. III
As per IEC 61010-2-030
Pollution degree
3
y 2000 m
Altitude
Degree of protection
Device only
IP20
IK
05
Radio-frequency communication ISM band 2.4 GHz
2.4 GHz to 2.4835 GHz
Channels
As per IEEE 802.15.4
11 to 26 0 dBm < 5 ms
Isotropic Radiated Power Maximum transmission time
Equivalent (EIRP)
Channel occupancy
Messages sent every
5 seconds minimum
Characteristics of measuring functions Function
Symbol
Performance category as per IEC 61557-12 (PMD-I/DD/K55/1)
Measuring range
Class
Active power Active energy
P
1 1 1
9 W to 63 kW
Ea
Total and partial 0 to 99999999.9 kWh
Current Voltage
I
40 mA to 63 A
U
0.5
Un ± 20 %
Power factor
PFA 1
0 to 1
70
Version: 1.0 - 02/07/2021 PLSED309005EN_04