MELSERVO-J4
Options/Peripheral Equipment
Power Factor Improving DC Reactor (FR-HEL, FR-HEL-H) Dimensions
GF-RJ GF
B
B-RJ
A
A-RJ
D or shorter (Note 3) D3
4-d mounting hole (Note 1)
P P1
B
Terminal screw size
Variable dimensions [mm]
Wire size (Note 4) [mm 2 ] 2 (AWG 14) 3.5 (AWG 12) 5.5 (AWG 10) 8 (AWG 8) 14 (AWG 6) (Note 2)
Mass [kg]
Model
W W1
H
D D1 D2 D3
d
H±2
FR-HEL-3.7K
77 55 92 82 66 57 37 M4 1.5 M4
FR-HEL-7.5K 86
60 113 98 81
72 43 M4 2.5 M5
FR-HEL-11K
105 64 133 112 92 79 47 M6 3.3
M6
D2 D1±2
W1 W±2
FR-HEL-15K
105 64 133 115 97 84 48.5 M6 4.1 M6
4-d mounting hole (Note 1)
C
D or shorter
D3 or shorter (Note 3)
P1
P
Terminal screw size
H±2
Variable dimensions [mm]
Wire size (Note 4) [mm 2 ]
Mass [kg]
Model
W W1 105 64
H
D D1 D2 D3
d
7
D2 D1±2
W±2 W1
FR-HEL-22K FR-HEL-30K
93 175 117 104 115 M6 5.6 M10
22 (AWG 4) 38 (AWG 2)
114 72 100 200 125 101 135 M6 7.8
M10
D or shorter
4-d mounting hole (Note 1)
(D3)
P P1
D
H±2.5
Terminal screw size
Variable dimensions [mm]
Wire size (Note 4) [mm 2 ]
Mass [kg]
Model
W W1 d FR-HEL-H1.5K 66 50 100 80 74 54 37 M4 1.0 M3.5 2 (AWG 14) FR-HEL-H2.2K 76 50 110 80 74 54 37 M4 1.3 M3.5 2 (AWG 14) H D D1 D2 D3
W±2.5 W1
D1±1 D2
Notes: 1. Use this mounting hole for grounding. 2. When using FR-HEL-15K, select a wire of 8 mm 2 (AWG 8) for MR-J4-700GF/B/A, and 14 mm 2 (AWG 6) for MR-J4-11KGF/B/A. 3. This indicates the maximum dimension. The dimension varies depending on the bending degree of the input/output lines. 4. The wire size is applicable when 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wires) is used.
5-81