Industrial Control Panel Solutions Catalog

TeSys™ motor control and protection solutions

Motor circuit protectors

Fusible discon- nects

Non-fused discon- nects TeSys VLS, MD

Manual motor protectors

Combination motor controllers

Circuit breakers

Fuse holders

Overload relays

Motor starters

Contactors

PPB, Multi 9 TeSys BV4 TeSys GS

TeSys DF TeSys GV TeSys D, F TeSys D TeSys H TeSys U

Range name

Product reference prefix

B, M9

BV4

GS

VLS, MD

DF

GV

LC

LR

LZ

LU

Motor starter structure - 4 functions:

— — —

Disconnect

(2)

— — —

(1)

(2)

Short-circuit protection

— — — — — —

Motor controller

Overload protection — Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller. — — — — —

Disconnect + fuses + contactor + overload relay Motor HP 460 V 1/2 3/4 1

1-1/2

2

3

5

7-1/2

10

Full load current (NEC Table 430.250)

1.1 A

1.6 A

2.1 A

3 A

3.4 A

4.8 A

7.6 A

11 A

14 A

Fused disconnect (UL 98)

GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DU3

Fuse class/ampacity

CC 3 A CC 4.5 A CC 6 A

CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A

J 25 A 100 kA

SCCR

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

Non-fused disconnect (UL 98)

VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2

Ampacity

60 A

60 A

60 A

60 A

60 A

60 A

60 A

60 A

60 A

50 kA (60 A J)

50kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

50 kA (60 A J)

SCCR (max fuse/class)

Fuse holder

DFCC3

DFCC3

DFCC3

DFCC3

DFCC3

DFCC3

DFCC3

DFCC3 9080FB3611J

Fuse class/ampacity

CC 3 A CC 4.5 A CC 6 A

CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A

J 25 A 200 kA

SCCR

200 kA

200 kA

200 kA

200 kA

200 kA

200 kA

200 kA

200 kA

Contactor (2)

LC1D09

LC1D09

LC1D09

LC1D09

LC1D09

LC1D09

LC1D09

LC1D12

LC1D18

SCCR with fuse shown Thermal overload class 10

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

LRD06

LRD07

LRD07

LRD08

LRD08

LRD10

LRD12

LRD16

LRD21

Overload range

1–1.6 A 1.6–2.5 A 1.6–2.5 A 2.5–4 A 2.5–4 A

4–6 A

5.5–8 A 100 kA

9–13 A 100 kA

12–18 A 100 kA

SCCR with fuse shown

100 kA

100 kA

100 kA

100 kA

100 kA

100 kA

Electronic overload

LR9D02

LR9D02

LR9D08

LR9D08

LR9D08

LR9D08

LR9D32

LR9D32

LR9D32

Overload range

0.4–2 A 0.4–2 A 1.6–8 A 1.6–8 A 1.6–8 A 1.6–8 A 6.4–32 A 6.4–32 A 6.4–32 A

SCCR with fuse shown 100 kA Notes: (2) Complete the contactor part number by adding the coil voltage suffix from TABLE A. For example LC1D09G7 includes a 120 VAC coil. 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA

TABLE A: Voltage coil codes for TeSys LC1 Contactors

24 V

24 V

120 V 100–250 V

LC1 Contactor

AC

DC

AC

AC/DC

D09–D32

B7

BL

G7

KUE

D40A–D65A D80–D150 F115–F330

B7

BBE

G7

KUE

B7

BD

G7

BD

G7

Consult the Schneider Electric Digest for more product selection options and information.