Industrial Control Panel Solutions Catalog
TeSys™ motor control and protection solutions
Motor circuit protectors
Fusible discon- nects
Non-fused discon- nects TeSys VLS, MD
Manual motor protectors
Combination motor controllers
Circuit breakers
Fuse holders
Overload relays
Motor starters
Contactors
PPB, Multi 9 TeSys BV4 TeSys GS
TeSys DF TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Range name
Product reference prefix
B, M9
BV4
GS
VLS, MD
DF
GV
LC
LR
LZ
LU
Motor starter structure - 4 functions:
—
— — —
Disconnect
—
(2)
— — —
(1)
(2)
Short-circuit protection
— — — — — —
—
Motor controller
Overload protection — Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller. — — — — —
Disconnect + fuses + contactor + overload relay Motor HP 460 V 1/2 3/4 1
1-1/2
2
3
5
7-1/2
10
Full load current (NEC Table 430.250)
1.1 A
1.6 A
2.1 A
3 A
3.4 A
4.8 A
7.6 A
11 A
14 A
Fused disconnect (UL 98)
GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DDU3 GS1DU3
Fuse class/ampacity
CC 3 A CC 4.5 A CC 6 A
CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A
J 25 A 100 kA
SCCR
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
Non-fused disconnect (UL 98)
VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2 VLS3P063R2
Ampacity
60 A
60 A
60 A
60 A
60 A
60 A
60 A
60 A
60 A
50 kA (60 A J)
50kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
50 kA (60 A J)
SCCR (max fuse/class)
Fuse holder
DFCC3
DFCC3
DFCC3
DFCC3
DFCC3
DFCC3
DFCC3
DFCC3 9080FB3611J
Fuse class/ampacity
CC 3 A CC 4.5 A CC 6 A
CC 9 A CC 10 A CC 15 A CC 20 A CC 30 A
J 25 A 200 kA
SCCR
200 kA
200 kA
200 kA
200 kA
200 kA
200 kA
200 kA
200 kA
Contactor (2)
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D12
LC1D18
SCCR with fuse shown Thermal overload class 10
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
LRD06
LRD07
LRD07
LRD08
LRD08
LRD10
LRD12
LRD16
LRD21
Overload range
1–1.6 A 1.6–2.5 A 1.6–2.5 A 2.5–4 A 2.5–4 A
4–6 A
5.5–8 A 100 kA
9–13 A 100 kA
12–18 A 100 kA
SCCR with fuse shown
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
Electronic overload
LR9D02
LR9D02
LR9D08
LR9D08
LR9D08
LR9D08
LR9D32
LR9D32
LR9D32
Overload range
0.4–2 A 0.4–2 A 1.6–8 A 1.6–8 A 1.6–8 A 1.6–8 A 6.4–32 A 6.4–32 A 6.4–32 A
SCCR with fuse shown 100 kA Notes: (2) Complete the contactor part number by adding the coil voltage suffix from TABLE A. For example LC1D09G7 includes a 120 VAC coil. 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
TABLE A: Voltage coil codes for TeSys LC1 Contactors
24 V
24 V
120 V 100–250 V
LC1 Contactor
AC
DC
AC
AC/DC
D09–D32
B7
BL
G7
KUE
D40A–D65A D80–D150 F115–F330
B7
BBE
G7
KUE
B7
BD
G7
BD
G7
Consult the Schneider Electric Digest for more product selection options and information.