Industrial Control Panel Solutions Catalog
TeSys™ motor control and protection solutions
Motor circuit protectors
Manual motor protectors
Combination motor controllers
Circuit breakers
Fusible disconnects
Non-fused disconnects TeSys VLS, MD
Fuse holders
Overload relays
Motor starters
Contactors
Range name
PPB, Multi 9 TeSys BV4 TeSys GS
TeSys DF TeSys GV TeSys D, F TeSys D TeSys H TeSys U
Product reference prefix
B, M9
BV4
GS
VLS, MD
DF
GV
LC
LR
LZ
LU
Motor starter structure - 4 functions:
—
— — —
Disconnect
—
(2)
— — —
(1)
(2)
Short-circuit protection
— — — — — —
—
Motor controller
Overload protection — Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller. — — — — —
Type F combination motor controller Motor HP 460 V 1/2 3/4 1
1-1/2
2
3
5
7-1/2
10
15
20
25
30
40
Full load current (NEC Table 430.250)
1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A 21 A 27 A 34 A 40 A 52 A
SCCR 480 Y/277 V 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA
50 kA (2)
50 kA (2)
50 kA (2)
65 kA 65 kA 65 kA 65 kA
Manual motor protector (1)
GV2P06 GV2P07 GV2P07 GV2P08 GV2P08 GV2P10 GV2P14 GV2P16 GV2P20 GV2P21 GV3P32 GV3P40 GV3P50 GV3P65
Overload range
1–1.6 A
1.6–2.5 A
1.6–2.5 A
2.5–4 A
2.5–4 A
4–6.3 A
6–10 A
9–14 A
13–18 A
17–23 A
23–32 A
30–40 A
37–50 A
48–65 A
Contactor ( 3) LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D18 LC1D25 LC1D25 LC1D40A LC1D40A LC1D50A LC1D65A
Notes: (1) Type F combination requires use of GV1G09 line spacer for GV2 or GV3G66 line spacer for GV3. Permissible to use GV2G busbars with GV1G09 for the GV2 to reduce wiring installation efforts. (2) Type F combination SCCR is 42 kA 480Y / 277V when using GVG2 busbars with GV1G09 on GV2P16 to GV2P21. (3) Complete the contactor part number by adding the coil voltage suffix from TABLE A. For example, LC1D09G7 includes a 120 VAC coil.
TABLE A: Voltage coil codes for TeSys LC1 Contactors
24 V
24 V
120 V 100–250 V
LC1 Contactor
AC
DC
AC
AC/DC
D09–D32
B7
BL
G7
KUE
D40A–D65A D80–D150 F115–F330
B7
BBE
G7
KUE
B7
BD
G7
BD
G7
Type E combination motor controller Motor HP 460 V 1/2 3/4
1
1-1/2
2
3
5
7-1/2
10
15
20
Full load current (NEC Table 430.250)
1.1 A 1.6 A 2.1 A
3 A
3.4 A 4.8 A 7.6 A
11 A
14 A
21 A
27 A
Base (1)
LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB32 LUB32 LUB32 LUB32
Trip unit ( 2)
LUCA1X LUCA05 LUCA05 LUCA05 LUCA12 LUCA12 LUCA12 LUCA18 LUCA32 LUCA32 LUCA32
Overload range
0.3–1.4 A 1.25–5 A 1.25–5 A 1.25–5 A 3–12 A 3–12 A 3–12 A 4.5–18 A 8–32 A 8–32 A 8–32 A
SCCR 480 Y/277 V 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA Notes: (1) Type E combination requires use of LU9SP0 line spacer or GV1G09 line spacer. Permissible to use GV2G busbars with GV1G09 to reduce wiring installation efforts. (2) Complete the contactor part number by adding the coil voltage suffix from TABLE B. For example, LUCA12FU includes a 120 VAC coil.
TABLE B: Voltage coil codes for TeSys U Starters
24 V
24 V
120–240 V
AC
DC
AC/DC
LUC Trip units
B
BL
FU
Consult the Schneider Electric Digest for more product selection options and information.