Industrial Control Panel Solutions Catalog

TeSys™ motor control and protection solutions

Motor circuit protectors

Manual motor protectors

Combination motor controllers

Circuit breakers

Fusible disconnects

Non-fused disconnects TeSys VLS, MD

Fuse holders

Overload relays

Motor starters

Contactors

Range name

PPB, Multi 9 TeSys BV4 TeSys GS

TeSys DF TeSys GV TeSys D, F TeSys D TeSys H TeSys U

Product reference prefix

B, M9

BV4

GS

VLS, MD

DF

GV

LC

LR

LZ

LU

Motor starter structure - 4 functions:

— — —

Disconnect

(2)

— — —

(1)

(2)

Short-circuit protection

— — — — — —

Motor controller

Overload protection — Notes: (1) When used as a Type D combination motor controller. (2) When used as a Type E or F combination motor controller. — — — — —

Type F combination motor controller Motor HP 460 V 1/2 3/4 1

1-1/2

2

3

5

7-1/2

10

15

20

25

30

40

Full load current (NEC Table 430.250)

1.1 A 1.6 A 2.1 A 3 A 3.4 A 4.8 A 7.6 A 11 A 14 A 21 A 27 A 34 A 40 A 52 A

SCCR 480 Y/277 V 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA

50 kA (2)

50 kA (2)

50 kA (2)

65 kA 65 kA 65 kA 65 kA

Manual motor protector (1)

GV2P06 GV2P07 GV2P07 GV2P08 GV2P08 GV2P10 GV2P14 GV2P16 GV2P20 GV2P21 GV3P32 GV3P40 GV3P50 GV3P65

Overload range

1–1.6 A

1.6–2.5 A

1.6–2.5 A

2.5–4 A

2.5–4 A

4–6.3 A

6–10 A

9–14 A

13–18 A

17–23 A

23–32 A

30–40 A

37–50 A

48–65 A

Contactor ( 3) LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D18 LC1D25 LC1D25 LC1D40A LC1D40A LC1D50A LC1D65A

Notes: (1) Type F combination requires use of GV1G09 line spacer for GV2 or GV3G66 line spacer for GV3. Permissible to use GV2G busbars with GV1G09 for the GV2 to reduce wiring installation efforts. (2) Type F combination SCCR is 42 kA 480Y / 277V when using GVG2 busbars with GV1G09 on GV2P16 to GV2P21. (3) Complete the contactor part number by adding the coil voltage suffix from TABLE A. For example, LC1D09G7 includes a 120 VAC coil.

TABLE A: Voltage coil codes for TeSys LC1 Contactors

24 V

24 V

120 V 100–250 V

LC1 Contactor

AC

DC

AC

AC/DC

D09–D32

B7

BL

G7

KUE

D40A–D65A D80–D150 F115–F330

B7

BBE

G7

KUE

B7

BD

G7

BD

G7

Type E combination motor controller Motor HP 460 V 1/2 3/4

1

1-1/2

2

3

5

7-1/2

10

15

20

Full load current (NEC Table 430.250)

1.1 A 1.6 A 2.1 A

3 A

3.4 A 4.8 A 7.6 A

11 A

14 A

21 A

27 A

Base (1)

LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB12 LUB32 LUB32 LUB32 LUB32

Trip unit ( 2)

LUCA1X LUCA05 LUCA05 LUCA05 LUCA12 LUCA12 LUCA12 LUCA18 LUCA32 LUCA32 LUCA32

Overload range

0.3–1.4 A 1.25–5 A 1.25–5 A 1.25–5 A 3–12 A 3–12 A 3–12 A 4.5–18 A 8–32 A 8–32 A 8–32 A

SCCR 480 Y/277 V 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA Notes: (1) Type E combination requires use of LU9SP0 line spacer or GV1G09 line spacer. Permissible to use GV2G busbars with GV1G09 to reduce wiring installation efforts. (2) Complete the contactor part number by adding the coil voltage suffix from TABLE B. For example, LUCA12FU includes a 120 VAC coil.

TABLE B: Voltage coil codes for TeSys U Starters

24 V

24 V

120–240 V

AC

DC

AC/DC

LUC Trip units

B

BL

FU

Consult the Schneider Electric Digest for more product selection options and information.

15

15

Made with FlippingBook - Online catalogs