Altivar Soft Starter ATS480
Altivar Soft Starter ATS480 Soft starters for asynchronous motors Options: Line chokes
Presentation, references
Line chokes The use of line chokes is recommended in particular when installing several soft starters on the same line supply to limit low frequency interference that may affect low level loads. The inductance values are defined for a voltage drop between 3% and 5% of the nominal line voltage. Install the line choke between the line contactor and the soft starter.
VZ1L150U170T F19_ACCESSORIES_CPODA2016006
References Corresponding soft starter
Line choke Inductance value
Reference
Weight
Nominal current
Degree of protection
kg/ lb
mH 1.7
A
VZ1L015UM17T
ATS480D17Y
15
IP20
2.100/ 4.630 4.100/ 9.039 5.100/ 11.2 8.000/ 17.6 14.9/ 32.8 24.3/ 53.5 28.9/ 63.7 37.0/ 8 1.5 66.0/ 145.5 80.0/ 176.3
VZ1L030U800T
ATS480D22Y
0.8
30
IP20
VZ1L040U600T
ATS480D32Y…D38Y 0.6
40
IP20
VZ1L070U350T
ATS480D47Y…D62Y 0.35
70
IP20
VZ1L150U170T
ATS480D75Y…C14Y 0.17
150
IP00
VZ1L250U100T
ATS480C17Y…C25Y 0.1
250
IP00
VZ1L325U075T
ATS480C32Y
0.075
325
IP00
VZ1L530U045T
ATS480C41Y…C48Y 0.045
530
IP00
VZ1LM10U024T
ATS480C59Y…M10Y 0.024
1025
IP00
VZ1LM14U016T
ATS480M12Y
0.016
1435
IP00
Combinations: page 27
Dimensions: page 45
32