Selection criteria (continued) Altivar Soft Starter ATS480 Soft starters for asynchronous motors Selection of ATS480 commercial reference

Selection of ATS480 commercial reference Once the appropriate application has been selected from the previous page, select the Altivar Soft Starter ATS480 from page 18 according to the supply voltage and the motor power. Check that the rated motor current is lower than the operational current of the ATS480. The Altivar Soft Starter ATS480 is designed to respect the operations shown in the table in the “Select normal duty or heavy duty application” section on page 13 without triggering an overheat error and without bypass at 40 °C/ 104 °F max. and at an altitude of 1,000 m/ 3,280 ft . Above those limits it is necessary to derate the operational current of the soft starter as follows:

b derating of 2% per °C above 40 °C/ 104 °F up to 60 °C/ 140 °F b derating of 1% per 100 m/ 328 ft up to 4,000 m/ 13,124 ft

Breakdown of ATS480 product reference

ATS 480 D 32 Y

Product range ATS

Altivar Soft Starter

Type 480 Factor for current rating D current x 1 C current x 10 M current x 100 Current multiplicand 10-11-12-….....66-75-79-88 Mains voltage Y 208 to 690 Vac Current x 1 Current x 10 Current x 100 208 to 690 VAC

For example, for the reference ATS480C17Y, the current rating is 170 A (17 x 10). The current rating is defined as the rated operational current in normal duty, in-line, not bypassed at 40 °C/ 104 °F.

Optimizing the selection when bypassed When bypassed, the Altivar Soft Starter ATS480 rating selection can be optimized. The thyristors were chosen not only to supply the motor during starting and stopping but also during steady state operations. However, the soft starter can be bypassed by a contactor at the end of starting (to limit the heat dissipated by the soft starter). The bypass contactor is controlled by the soft starter: the current measurements and monitoring mechanisms remain active when the soft starter is bypassed. When bypassed, the ATS480 can supply a higher power motor. Example of an 11 kW motor at 400 V: b In normal duty: v Select ATS480D22Y if not bypassed v Select ATS480D17Y if bypassed and check that the current limiting is in accordance with the starting requirement b In heavy duty: v Select ATS480D32Y if not bypassed v Select ATS480D22Y if bypassed and check that the current limiting is in accordance with the starting requirement

Selection guide: page 4

References: page 18

Combinations: page 27

Coordination: page 35

Dimensions: page 45